HVAC Inspection Guide

STANDARDS OF PRACTICE

The International Standards of Practice for inspecting the HVAC systems is located at www.nachi.org/sop.

SIZE AND CATEGORY

Gas appliances are categorized so that the proper venting system can be selected. There are four categories based upon the pressure produced in the vent and whether or not the flue gas temperatures create condensation.

You'll commonly find Category I and Category IV furnaces and boilers in U.S. houses. Category I does not produce condensate. Category IV operates with a positive vent pressure and condenses flue gases, and their flue vent pipes are made of PVC plastic.

Type B vents are designed for venting non-condensing gas appliances equipped with a draft hood or fan-assisted appliances with a non-positive vent pressure.

Heating and cooling equipment and appliances must be sized in accordance with the Manual S and Manual J of the Air Conditioning Contractors of America.

Observation

The furnace in the furnace room is a Category I appliance that operates under a negative or neutral vent pressure. It's not a condensing appliance. It uses a draft inducer fan. 

You may want to confirm this observation by checking the manufacturer's information sticker for the appliance. On this appliance, it's located at the front cover at the blower fan location.

Observation

The furnace is 80% efficient. You may calculate the efficiency by dividing output BTU by input BTU on the manufacturer's data sticker. Or, there may be an efficiency sticker attached, such as the yellow sticker.

HVAC efficiency 2

HVAC sticker 2

 

 

ACCESS

Heating and cooling equipment and appliances must be accessible for inspection, routine maintenance, repairs and replacements.

Access - Inspection, Routine Maintenance, Repairs and Replacements.

Observation

The manufacturer requires 24 inches in front of the appliance for access.

2015 IRC M1305 recommends that the furnace have a level working space of at least 30 inches by 30 inches in the front of the appliance. Municipalities may require a minimum of 30 clear inches in front of the furnace, which can be accomplished in a small room if the door to the room opens in front of the furnace.

The furnace in the furnace room is accessible for service.

Observation

There are combustible wall materials in close proximity to the gas-fired furnace appliance. According to the manufacturer, the minimum clearance from the back-side of the appliance is 0 inches.

Observation -  Combustible wall materials in close proximity to the gas-fired furnace appliance

 

 

AUXILIARY DRAIN PAN

Category IV appliances produce condensate. A condensing appliance must be provided with an auxiliary drain pan where structural damage to a home's building components may occur, if the condensate drainage leaks. A pan is not necessary if the appliance has an automatic shut-down device installed.

Observation

A pan is not needed at this installation.

 

 

CONDENSATE PUMP

Condensate pumps should be connected to the appliance such that when the pump fails, the appliance shuts off. The condensate pump should have an overflow shutoff capability.

Observation

There's no condensate drainage or pump installed for the central air conditioner's evaporator.

HVAC access clearance

 

 

COMBUSTION AIR

Combustion air is necessary for the complete combustion of fuel gas, dilution of flue gases, and ventilation of gas-fired appliances and the space in which they are installed. A lack of combustion air can cause the incomplete combustion of fuel, malfunction of an appliance, and spillage of flue gases. Gas-fired appliances often compete with other equipment and systems for available combustion air and makeup air through a house. Supplying makeup air can help natural-draft appliances by compensating the effect of the powered exhaust appliances and equipment in the house, including fireplaces, exhaust fans, ventilation systems, clothes dryers and similar appliances and equipment.

There are five methods of supplying combustion air listed in the 2015 IRC G2407, ranging from simple to complex:

  • all indoor air,
  • all outdoor air,
  • combination indoor and outdoor air,
  • mechanical combustion air supply, and
  • engineered design.

These methods of supplying combustion air applies mostly to natural-draft atmospheric-burner-design appliances and Category 1 fan-assisted appliances. Category 2, 3, and 4 appliances must be provided with combustion air as required by the manufacturer's instructions.

METHODS OF COMBUSTION AIR

Indoor Combustion Air

The required volume of indoor air to be used as combustion air is determined in five different ways according to 2017 IRC G2407.5, except when the infiltration rate is known to be less than 0.40 air exchanges per hour (ACH). The terms "confined space", "unconfined space", and "unusually tight construction" are no longer used.

Require volume of indoor air is determined by two methods, unless the known infiltration rate is less than 0.40 ACH:

  • one is based upon the actual air infiltration rate measured in the house, and
  • the other is based on the familiar 50 cubic feet per 1,000 Btu/h.

Openings to Connect Indoor Spaces

Where openings are used to connect adjacent indoor spaces on the same floor for the purpose of increasing the available volume of air, the familiar high and low openings may be provided. The openings must be permanently open, and each opening must be at least 100 square inches in size. One opening must be within 12 inches of the top and one opening 12 inches of the bottom of the enclosure.

Outdoor Combustion Air Opening

Openings directly connected to the outdoor air or to spaces that are naturally ventilated with outdoor air, such as crawlspaces or attics, are acceptable. The combustion air openings should be located to prevent blockage. The opening could be one-permanent opening or two-permanent high-low openings. There are various types of opening combinations that may include indoor and outdoor spaces to supply combustion air.

Not Required

Home inspectors are not required to calculate the air for combustion, ventilation, and dilution of flue gases for appliances.

Observation

The combustion air opening at the exterior wall of the furnace room may cause pipe freezing problems for cold climates.

Observation - Combustion Air Opening

Observation

There are 2 air registers on the exterior of the house, on the wall opposite the furnace room. One is blocked with debris.

Observation - 2 Air Registers

 

 

MAKEUP AIR

Makeup air is needed where clothes dryers, kitchen exhaust fans, chimneys, and other exhaust and ventilation systems may interfere with the appliance operation. Not enough makeup air may cause negative pressures to develop and may interfere with appliance venting, creating a loss of draft at appliance vents and chimneys or causing combustion byproducts to backdraft into the house. Gas-fired appliances are often in competition with other systems for the available combustion air and makeup air that flows through the house building envelope. And natural draft appliances could starve for air. Supplying makeup air will help prevent negative pressures with a space from developing.

Note the following systems that may deplete combustion air: bathroom exhaust fan at 80 CFM, range hood at 100 CFM, clothes dryer at 200 CFM, and a fireplace chimney at 600 CFM.

Observation

The combustion air opening at the exterior wall of the furnace room may cause pipe freezing problems for cold climates.

Observation - Combustion Air Opening

 

 

PROTECTION FROM FUMES

Chemicals that generate corrosive or flammable products should be removed from rooms providing combustion air and dilution air, particularly for natural draft appliances. Chemicals could contaminate the indoor combustion air by combining with water vapor in the combustion gases to produce acids that can damage appliance components, vents, chimneys and connectors.

Observation

There are cans of chemicals in the utility room. They should be removed to help prevent corrosion of the HVAC system.

HVAC chemical paint cans

 

 

GAS PIPING

Observation

Unconventional installation of the fuel supply pipes, materials, components, valves, and support at the furnace and water heater tank.

Observation - Unconventional installation of the fuel pipes at the furnace and water heater tank

SEDIMENT TRAP

A sediment trap must be installed downstream of the gas shutoff valve as close to the furnace as possible. The trap could be a simple tee fitting with a nipple of any length and a cap.

Observation

There is not a sediment trap installed. Defect.

HVAC sediment trap

APPLIANCE SHUTOFF VALVES

Shutoff valves must not be installed in concealed locations and furnace plenums. Shutoff valves must be accessible, located in the same room as the appliance, and protected from damage. The shutoff valve must be within 6 feet of the appliance. It must be located upstream of the union or connector device.

 

Observation

There is no shutoff valve installed.

HVAC shutoff valve

 

FLEXIBLE GAS CONNECTORS vs. CSST

HVAC CCST

  • Corrugated Stainless Steel Tubing (CSST) is observed in the garage and under the deck.
  • There is a flexible connector at the HVAC equipment in the furnace room.

CSST should not be confused with natural gas appliance flexible connectors. Flexible connectors are used to attach moveable appliances to the gas piping system. CSST is typically routed beneath, through or alongside floor joists in the basement, inside interior wall cavities and on top of ceiling joists in attic spaces.

CSST piping systems must be installed in accordance with the terms of their approval, the conditions of listing, the manufacturer’s instructions, and the IRC.

CSST is a flexible, stainless steel pipe used to supply natural gas and propane in residential and commercial buildings. It is often coated with a yellow or black plastic coating.  CSST should not be confused with flexible gas appliance connectors that join an appliance to the gas supply line of a house.

CSST is safe when properly installed.

For more information about CSST, please refer to the Plumbing Inspection Guide.

Observation

The flexible gas line should not be installed within the furnace cabinet. Only solid gas piping should be connected to and installed within the cabinet.

Observation - Flexible gas line should not be installed within the furnace cabinet

Observation

The flexible gas line is extremely bent within the cabinet and is possibly damaged, but his flexible line should not be installed within the cabinet.

HVAC bent flexible pipe

APPLIANCE CONNECTIONS

Appliance fuel connectors should be installed according to the manufacturer's recommendations and code. The total length of a connector should not be greater than 6 feet.

A union fitting must be installed for appliances connected by a rigid metallic pipe.

 

Observation

There is not a union fitting installed.

Observation - No Union Fitting Installed

PIPING SUPPORTS

Piping must be supported at intervals no less than 6 feet.

 

Observation

There is inadequate support for the fuel pipes.

Observation - Inadequate support for the fuel pipes

 

 

VENTS

Type B vents are designed for venting non-condensing gas appliances equipped with a draft hood or fan-assisted appliances with a non-positive vent pressure.

Type BW vents are for gas-fired wall furnaces. They are oval shaped to be fitted into a wall cavity.

Type L vents are for oil-burning appliances.

Type B and BW are double-walled and air-insulated vent pipe systems with aluminum inner walls and galvanized steel outer pipe walls.

 

Observation

The gas vent pipe from the water heater tank is improperly sloped. There is a disconnection at the elbow. This vent pipe is connected to the shared vent stack with the furnace.

Observation - Gas vent pipe improperly sloped

Cloth duct tape is not permitted to be installed on fuel-burning appliance vent pipes. Many municipalities do not allow metal foil tape either.

HVAC vent disconnect

Single wall vent pipe must be connected with 3 sheet metal screws at each joint. 

Single wall flue vents require a six-inch minimum of clearance to combustibles, and B-vent (double wall) requires minimum 1-inch clearance.

INSULATION SHIELD

Observation

There is no insulation shield installed in the attic around the flue vent pipe.

HVAC insulation shield

Where the vent passes through insulation in an attic, the insulation shield must be terminate at least 2 inches above the insulation and must be secured in place.

FIREBLOCKING & CLEARANCE

Observation

Electrical cable is in contact with the vent pipe of the furnace.

2J7A1414

Observation

Missing fireblocking at the furnace vent chimney pipe where it penetrates the ceiling of the furnace room.

Observation - Missing fireblocking

Observation

Inadequate clearance from combustibles at the gas vent stack for the furnace at the drywall and wooden structural components.

The clearance between gas vents and combustible materials is listed by the manufacturer, but is typically 1 inch for Type B.

Observation - Inadequate clearance from combustibles

HVAC pipe clearance

Openings around vents, chimneys, pipes, ducts, wires, and cables at the ceiling and floor levels must be fireblocked with an approved material to resist the free passage of flames and combustion products.

CHIMNEY TERMINATION

Observation

The gas vent violates the required clearance from the nearly vertical obstruction.

Observation - Nearly vertical obstruction

Observation

There is a missing vent cap at the furnace gas vent (chimney).

Observation - Vent Cap

The gas vent (chimney for the furnace) should extend at least 3 feet above the highest point where it passes through a roof and at least 2 feet higher than any portion of the house within a horizontal distance of 10 feet.

Gas vents that are less than 12 inches in diameter and not closer than 8 feet from a vertical wall or similar obstruction must terminate at least 1 foot above the roof that has a slope from 0:12 to 6:12. The gas vent must have a listed cap.

 

 

DUCTS

Duct systems for HVAC equipment are installed in accordance with the ACCA Manual D, the manufacturer, or other approved methods.

Observation

The opening between the duct and the floor sheathing creates an opening to the unconditioned crawlspace.

Observation - Opening to the unconditioned crawlspace

Observation

There is a crushed and damaged duct pipe in the ceiling of the kitchen.

HVAC crushed duct ceiling

Observation

The main trunk of the HVAC system in the attic space ends abruptly into a small-diameter round duct. The concern is a poor design of the duct that reduces friction and air disturbance and promotes smooth flow and distribution of air.

Observation - Poor design of the duct

Observation

There is a ceiling supply register that is blocked by drywall.
 
Observation - Ceiling supply register blocked by drywall

Observation

A notch was made at a structural component of an engineered truss. This is a structural defect observed from the attic space.
 
Observation - Defect

Observation

The round duct pipe in the ceiling is not sized correctly, and there is a large opening and loose connection.

HVAC crushed duct

Observation

There is a supply opening that is oddly located and partially covered by the heavy water pressure tank. This supply duct opening is missing a floor register.
 
Observation - Supply duct opening is missing a floor register

Observation

There is loose connection at the duct to the right of the water heater tank.

Observation - Loose connection at the duct

Observation

There is a separated, disconnected elbow fitting in the round supply duct that is visible from the attic floor area.
 
Observation - Separated, disconnected elbow fitting in the round supply duct

FASTENED, SEALED AND SUPPORTED DUCTS

Observation

Duct should not be used for supporting pipes.

Observation - Duct should not be used for supporting pipes

Observation

Ducts are not air sealed.

Observation - Ducts are not sealed

Observation

There is an open HVAC duct located on the rear wall of the garage.

According to the International Residential Code 2015 M1601.6 Independent Garage HVAC Systems, furnaces or air-handling systems that supply air to living spaces shall not supply air to or return air from a garage. Circulation of air contaminated with objectionable odors, flumes or flammable vapors is prohibited because of potential health and safety hazards.

Observation - Open HVAC duct located on the rear wall of the garage

Observation

There is metal duct in the crawlspace that is not securely fastened. There are sections of duct that are loose to the touch.

Observation - Metal duct in the crawlspace not securely fastened

Observation

The flexible duct in the crawlspace is not supported adequately.

Observation -  Flexible duct in crawlspace not supported adequately

Observation

The metal duct in the crawlspace is not supported improperly, and it does not seem reliable.

Observation - Metal duct not supported properly

The joints, seams and connections in metallic and non-metalllic ducts must be securerly fastened and sealed with welds, gaskets, mastics, liquid sealants, or tapes. Tapes and mastics should be listed and marked with "UL 181 A-P" for tape, "181 A-M" for mastic or "181 A-H" for heat-sensitive tape.

Fastened, Sealed, and Supported Ducts

"181 B-FX" is for flexible ducts. Crimp joints for round metallic jucts should have a 1-inch lap and at least 3 sheet-metal screws or rivets at the joint.

Ducts require adequate support at regular intervals.

DUCT INSULATION

Observation

The ducts in unconditioned spaces, including the crawlspace and attic, are not insulated.

Observation - Ducts are not insulated

The HVAC ductwork, including supply and return, located in unconditioned spaces, including the attic and crawlspaces, should be insulated with at least an R-8. Ductwork located completely within the building thermal envelope is not required to be insulated.

Duct insulation should not pass through an opening in a ceiling, floor or wall that is fireblocked.

VIBRATION

Observation

The vibration material observed above the furnace is stretched tightly without any room for movement and flexibility.

Observation - Vibration material

Observation

The vibration material observed from the attic space should not be located there. This vibration material should be accessible for easy inspection and service, if needed. The vibration material is very tight and has no material for flexibility.

Observation - Vibration material

CLEARANCE

Observation

Clearances for supply plenum and ducts to combustible materials are in accordance to manufacturer's instructions and typically apply within 3' of central heating furnace. Typical clearance where applicable is one inch.

Observation - Inadequate clearance

RETURN AIR OPENINGS

Observation

There should not be a return duct register installed in the kitchen.

Observation - There should not be a return duct register installed in the kitchen

There is an exception at 2017 IRC M1602.2 where there's at least 10 feet of clearance from a cooking appliance and the opening serves the kitchen only.

Observation

There should not be a return duct register installed in the furnace room, particularly when there's competition for air with the clothes dryer and natural-draft water heater tank. Hazardous back-drafting could result.

Observation - Return duct register installed in the furnace room

Observation

The return register at the duct to the left of the furnace and at the ceiling is within 10 feet of the draft hood of the water heater tank located in the same space as the return register.

Observation - Within 10 feet of the draft hood of the water heater tank

Return air openings should be located at least 10 feet in any direction from a combustion chamber or draft hood on an fuel-burning appliance in the same room.

The return air must not be taken from a kitchen, bathroom, closet, garage, mechanical room, boiler room, furnace room, or unconditioned attic space.

BUILDING CAVITIES

Nearly all building codes restrict the use of cavity spaces as supply ducts. However, it has been common practice to use cavity spaces as return-air pathways. Building cavities used as return-air plenums is one of the leading causes of duct leakage in homes today.

Still commonly used is the panned floor joist. Using floor joists as return ducts by panning can cause leakage because negative pressure in the cavity will draw air from the outside into the cavity through the construction joints of the rim area at the end of the joist cavity.

Cavities (or interstitial spaces) within walls are also sometimes used as supply- or return-air pathways. These cavities often create a connection of inside air with outside air from an attic or crawlspace. It is very difficult to make such cavity spaces airtight. When cavity spaces are used as return-air pathways or supply-air ducts, a few issues will arise.

Building Cavities Used as Supply or Return Ducts

Observation

There is a wall cavity and joist bays being used as a return pathway for the furnace duct.
 
According to 2015 IRC 1601.1, wall cavities and joist bays must not be used as air supply plenums. Learn how to inspect building cavities used as supply or return plenums.
 
Observation - Wall cavity being used as a return pathway for the furnace duct

 

 

CONTROLS

2015 IRC N1103 requires a programmable thermostat to be installed for the primary heating and cooling system.

The thermostat should be located in a central living room location to make the system run effectively.

Observation

The thermostat is located in the kitchen, which is an improper location.

Observation

The electrical shutoff switch for the furnace has a fuse device. Fuses are antiquated.

Observation - Fuses are antiquated

Observation

The electric receptacle is missing a clamp at the top of the electrical box.

Observation - Electric receptacle is missing a clamp

Observation

The electric wiring to the furnace cabinet is not properly installed, loose and not secure, and is missing a clamp connection to the cabinet.

Observation - Electric wiring to the furnace cabinet is not properly installed

Observation

There is a loose wire connection at the controls of the furnace, near the burner control component.

Observation - Loose wire connection

 

 

AIR FILTERING

FILTER ACCESS

The air filter should be accessible for inspection and service.

Observation

The air filter is not accessible. The refrigerant lines block the filter access location.

HVAC air filter

 

 

AIR CONDITIONING

CONDENSATE

Observation

The condensate drain lines and condensate pump are not installed.

AC condensate 

SUPPORT

Observation

The unit appears to be off-center of its support base.

AC base
 

CLEARANCE

Observation

Inadequate clearance between the air conditioner's outdoor compressor unit and the house and deck structures.

AC clearance

REFRIGERANT LINES

Observation

The pipes for the refrigerant vapor (suction) line should be insulated with at least an R-4 value.
Observation - Pipes for the refrigerant vapor (suction) line should be insulated with at least an R-4 value

Observation

The refrigerant lines are improperly attached to and supported by the ductwork.  

AC duct

Observation

The refrigerant lines in the crawlspace are inadequately supported. They are hanging.

AC support

Observation

There is a large open hole in the siding through which the refrigerant lines pass. This hole should be sealed to prevent vermin entry and moisture intrusion.  AC open hole

Observation

There's a squeezed, damaged area of the refrigerant line located near the air filter of the furnace. AC damage

 

Observation

There's no slack in the refrigerant lines.

AC slack

Observation

There are sections of pipe foam insulation on the suction line. There are damaged insulation in areas.

AC insulation

ELECTRICAL

Observation

The electrical disconnect is missing. According to NEC 440.14, there should be a electrical disconnect within sight and readily accessible of the air conditioning unit.

AC receptacle

Observation

The low-voltage line for the air conditioner system is damaged as observed from the crawlspace.

AC low voltage

Observation

There should be an GFCI-protected electric receptacle installed located within 25 feet of the air conditioner outdoor unit and on the same level as the equipment.

There is no exterior receptacle properly installed.

AC GFCI